kVA to kW Calculator
Convert kVA to kW or kW to kVA using the power factor.
Find the current for a given apparent power in kVA, or the kVA for a given current.
Choose single-phase or three-phase, enter the voltage and the kVA (or the amps for the other direction). kVA is apparent power, so no power factor is needed for this conversion.
Enter your values to see the result.
Want this tracked for you? UtilityControl logs your meters and costs automatically.
A 10 kVA three-phase generator at 400 V supplies up to 10 × 1000 ÷ (1.732 × 400) ≈ 14.4 A per phase. A 10 kVA single-phase unit at 230 V supplies about 43.5 A.
The result is the full-load current. Motors draw much more when they start, and cables and breakers need margins and local rules. Ask a qualified electrician before sizing them.
Written and reviewed by QLines, Cologne · Last reviewed
Single-phase: amps = kVA × 1000 ÷ volts. Three-phase: amps = kVA × 1000 ÷ (1.732 × volts). Example: 10 kVA at 400 V three-phase is about 14.4 A.
kVA is apparent power (volts × amps); kW is the real power that does work. kW = kVA × power factor. The kVA to kW calculator converts between them.
At 400 V three-phase about 144 A per phase; at 480 V about 120 A.